TECHNICAL DATA
Current Input (•n) : ../5A or ../1A
Frequency : Software selectable 50 or 60 Hz
Burden : <0.3 VA @ •n
Output Relay Rating : SPDT 5A, 250V AC/DC
Display : 7-Segment LED (3 + 1digit)
Indication (LEDs) : x10, pre-alarm, fault, fault start event, lo / hi trip
Operating Temp. : 0ºC ~ +55ºC
Humidity : 56 days at 93%RH, 40ºC non-condensing
IP Rating : IP54 (front panel)
PARAMETER SETTING (Phase OverCurrent)
•p> lo-set : 2% to 200% (step of 1%)
TM •p> : lo-set : time Multiplier 0.05 ~ 1.00
(step of 0.01, 5 IDMT + 1 DTL)
•p> : lo-set trip delay time : 0.03s ~ 20.0s
0.03s ~ 0.10s (step of 0.01s)
0.10s ~ 1.00s (step of 0.02s)
1.0s ~ 20.0s (step of 0.1s)
•p >> hi-set : OFF or 20% ~ 2000%
20% ~ 1000% (step of 10%)
1000% ~ 2000% (step of 100%)
•p >> hi-set trip delay time : 0.03s ~ 20.0s (same range as •p>)
PARAMETER SETTING (Earth Fault)
•e >: lo-set : 2% to 100% (step of 1%)
TM •e > : lo-set time Multiplier : 0.05 ~ 1.00
(step of 0.01, 5 IDMT + 1 DTL)
•e > : lo-set trip delay time : 0.03s ~ 20.0s
0.03s ~ 0.10s (step of 0.01s)
0.10s ~ 1.00s (step of 0.02s)
1.0s ~ 20.0s (step of 0.1s)
•e >> : hi-set : OFF or 20% ~ 1000% (step of 10%)
•e >> : hi-set trip delay time : 0.03s ~ 0.5s