TECHNICAL DATA
Measurement : True RMS Ampere
Rated Voltage Supply : 240Vac +/- 10%, (3 phase 4 wire)
415Vac +/- 10%, (3 phase 3 wire)
Rated frequency : 50 Hz
Output Contract : 1 C/O contract
Contract Rating : AC-15 240V / 1.5A, 415V / 0.95A
Weight : approx 210g
Operating temp. : -5° C ~ +40° C
Storage temp. : -10° C ~ +55° C
Enclosure Protection : IP20
Standard : EN/IEC 60947-5-1
SETTING RANGE
Over Voltage Setting : 250 ~ 310 Vac +/- 1%, (3 phase 4 wire)
430 ~ 530 Vac +/- 1%, (3 phase 3 wire)
Under VoltageSetting : 170 ~ 230 Vac +/- 1%, (3 phase 4 wire)
290 ~ 390 Vac +/- 1%, (3 phase 3 wire)
Delay time setting : 0.1 ~ 10.0 sec +/- 1%, (Over/Under Voltage)
2.0 sec Fixed (asymmetry trip)
< 1.0 sec (phase failure/phase sequence trip)